NFPA 96 — 2024 Edition Reference

NFPA 96 for Commercial Kitchens:
A Section-by-Section Compliance Reference

Every NFPA 96 rule that affects your commercial kitchen exhaust system, with the specific section number called out, explained in plain English, and tied to what compliance actually looks like.
Last reviewed: July 2026

NFPA 96 — formally the Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations — is the national rulebook for commercial cooking hoods, ducts, exhaust fans, and fire-suppression systems. Fire marshals enforce it. Insurance carriers reference it. For restaurant owners, hotel and hospital food service managers, school cafeteria operators, casino food and beverage directors, and property managers with a commercial kitchen tenant, NFPA 96 applies to the facility.

This page is a section-by-section reference for the rules in the standard that affect day-to-day operation, inspection, cleaning, documentation, equipment maintenance, and enforcement. A dedicated Penalties, Fines, and Consequences section covers what happens when a kitchen falls out of compliance — reinspection fees, forced-closure scenarios, and insurance claim consequences — pulled from Facilitec Southwest field experience across Texas, Oklahoma, Louisiana, New Mexico, and Arkansas since 1986.

A Note On The 2027 Edition

2027 Edition Watch: NFPA 96 is moving toward its next edition, and this page is being actively reviewed as that process continues. The next version is not yet the enforceable standard for inspections, cleaning, or documentation.

For commercial kitchens operating today, the enforceable standard remains the 2024 edition unless and until a newer edition is officially issued, adopted, and put into use by the authority having jurisdiction. That means the requirements explained throughout this page are based on the current edition that operators, service providers, and fire officials are working from now.

As the next edition moves forward, this reference will be updated so operators can quickly see what has changed, what is still current, and what matters for real-world compliance.

Official Source
For the official standard text and development record, visit NFPA 96 at NFPA.org. This Facilitec Southwest page is a practical reference written to explain the current edition in plain English while tracking future updates as they move through the standards process.
Quick Definitions

NFPA — National Fire Protection Association. NFPA 96 — its standard for commercial cooking ventilation. AHJ — Authority Having Jurisdiction (your local fire marshal). Exhaust system — the full grease path: hood, filters, ductwork, exhaust fan, rooftop discharge. Grease-laden vapor — the smoke and droplets from commercial cooking that condense as combustible grease inside the system.


Foundation

§ 4.1.5 Who Is Responsible for NFPA 96 Compliance

NFPA 96 names the equipment owner as the responsible party. Every other obligation in the standard flows from this rule.

“The responsibility for inspection, testing, maintenance, and cleanliness of the ventilation control, fire protection, and cooking appliances of the commercial cooking operations shall be that of the equipment owner.”

NFPA 96, 2024 Edition — Section 4.1.5.1

Section 4.1.5.2 permits the equipment owner to delegate that responsibility in writing — through the lease, a written use agreement, or a management contract — to the cooking operator, a management firm, or a managing individual. Verbal hand-offs don’t count. If your lease is silent on hood-system responsibility, the equipment owner remains responsible.

For most restaurant operators: if you operate the kitchen, your lease almost certainly assigns the obligation to you, even if the equipment is owned by the landlord. If you manage a property and are unsure who holds responsibility, review the lease before the next fire marshal visit.

FIELD NOTE
Across leases reviewed for new customers across the Southwest, the responsibility language is silent or unclear roughly four times out of ten. Property managers and operators sometimes both assume the other side is handling the file. Confirming who holds the obligation in writing — before the next fire marshal inspection — closes the most common gap in landlord-tenant disputes after a deficiency notice arrives.
The Inspection Cycle

§ 12.4 • Table 12.4 The Inspection Schedule by Cooking Volume

COOKING OPERATIONFREQUENCYEXAMPLES
Solid-fuel cookingMonthlyWood-fire pizza, BBQ smokehouses, charcoal grills
High-volume cookingQuarterly24-hour cooking, charbroiling, wok cooking
Moderate-volume cookingSemiannuallyMost standard sit-down restaurants
Low-volume cookingAnnuallyChurches, day camps, seasonal businesses, senior centers

“The entire exhaust system shall be inspected for grease buildup by a properly trained, qualified, and certified person(s) acceptable to the authority having jurisdiction and in accordance with Table 12.4.”

NFPA 96, 2024 Edition — Section 12.4

Table 12.4 is an inspection schedule, not a cleaning schedule. Cleaning is a separate event with a separate trigger — covered below. In solid-fuel and high-volume kitchens, the inspection and cleaning typically happen together every cycle. In lower-volume kitchens, inspection may not always trigger cleaning.

FIELD NOTE
The single most common mismatch between Table 12.4 and the kitchen is misclassification of cooking volume. A restaurant that calls itself a “standard sit-down” but runs a charbroiler for ten hours a day is operationally high-volume — the system loads with grease at the high-volume cadence regardless of how the menu is described. The companion guide on how often a commercial kitchen exhaust system should be cleaned covers the tier-identification logic in more depth.

§ 12.4 • 12.6.1 The Qualified-Person Rule

Both inspection and cleaning carry the same qualification requirement: work must be performed by a “properly trained, qualified, and certified person(s) acceptable to the authority having jurisdiction.”

That phrase is layered. Trained means structured instruction. Qualified means documented evidence of completed training. Certified means the credential was issued by a recognized body. Acceptable to the AHJ means your local fire marshal has the final say.

Two credentials are most widely recognized across the United States:

• IKECA — International Kitchen Exhaust Cleaning Association — issues the Certified Exhaust Cleaning Specialist (CECS) and Certified Exhaust Cleaning Inspector (CECI) credentials.

• Phil Ackland Training — a long-running industry training program. Facilitec Southwest is Phil Ackland Certified.

“Crews are trained” is not a credential. The standard requires named, certified persons — their names appear on the service label and written report for exactly that reason.

FIELD NOTE
“Bonded and insured” is not a credential. Across kitchens audited for new customers, the most common credential gap is a cleaning company that produces a written report but cannot name the certified person who performed the work. Section 12.6.1 requires the named, certified technician to appear on the service label and the written report — and a fire marshal who cannot match a named technician to a recognized credential will treat the cleaning as undocumented.
The Cleaning Cycle

§ 12.6.1.1 The Grease-Depth Thresholds That Trigger Cleaning

Cleaning is required when the inspection finds buildup over a depth-based threshold. The standard sets three different thresholds for three different surfaces.

0.002 inches

(about the thickness of a sheet of copy paper) — Hoods, filters, fans, ducts & appurtenances (Section 12.6.1.1.1)

0.078 inches

(two stacked dimes) — Other interior surfaces of the system (Section 12.6.1.1.3)

0.125 inches

(one-eighth of an inch) — on fan housings (Section 12.6.1.1.4)

The first threshold matters most in the typical kitchen. A paper-thin grease film on the hood, filters, fan, or ductwork is enough to require cleaning — far tighter than the “one-eighth inch” number sometimes cited in industry shorthand. That one-eighth inch is the fan-housing-only threshold from Section 12.6.1.1.4.

“A measurement system of deposition shall be established to trigger a need to clean when the exhaust system is inspected at the frequencies in Table 12.4.”

NFPA 96, 2024 Edition — Section 12.6.1.1

§ 12.6.2 Clean Before Heavy Contamination

“Hoods, grease removal devices, fans, ducts, and other appurtenances shall be cleaned to remove combustible contaminants prior to surfaces becoming heavily contaminated with grease or oily sludge.”

NFPA 96, 2024 Edition — Section 12.6.2

This forward-looking rule is what makes proactive scheduled cleaning the operational standard in high-volume kitchens. Waiting until grease crosses the Section 12.6.1.1.1 limit is the legal trigger — but Section 12.6.2 makes the standard’s intent clear: keep the system below that limit at all times.

§ 12.6.3 - 12.6.9 The Cleaning Process Itself

Once cleaning is triggered, the work has a defined process:

• Section 12.6.3 — Electrical switches must be locked out at the start of cleaning.

• Section 12.6.6 — Flammable solvents or cleaning aids cannot be used.

• Section 12.6.7 — Cleaning chemicals cannot be applied to fusible links or detection devices.

• Section 12.6.8 — After cleaning, the system cannot be coated with powder or other substance.

• Section 12.6.9 — All access panels and cover plates must be restored to normal operational condition.
• Section 12.6.11 — Dampers and diffusers must be positioned for proper airflow.

• Section 12.6.12 — All electrical switches and system components must be returned to an operable state.

A cleaning that skips electrical lockout, uses flammable solvents, sprays chemicals onto fusible links, leaves a coating, or fails to restore access panels is not a NFPA 96 cleaning — it’s a “hood-only” surface cleaning that creates the appearance of compliance without the substance.

See what is included in our commercial kitchen hood cleaning service.

Documentation

§ 12.6.13 The Service Label on the Hood

After every inspection or cleaning, an adhesive label must be securely attached to the hood. This is the first thing a fire marshal checks — and the first thing operators forget to verify.

“After an exhaust system is inspected or cleaned, an adhesive label shall be securely attached to the hood.”

NFPA 96, 2024 Edition — Section 12.6.13

Section 12.6.13.1 lists three required items: (1) date of service, (2) name of the person performing the work, (3) name, address, and phone number of the service provider. Section 12.6.13.2 requires the label to remain affixed until the next inspection or cleaning — it’s a continuous, in-place record, not a one-time receipt.

§ 12.6.10 Service Tags at Each Access Panel

“When an access panel is removed, a service company label or tag preprinted with the name of the company and giving the date of inspection or cleaning shall be affixed near the affected access panels.”

NFPA 96, 2024 Edition — Section 12.6.10

On a complex system with multiple access panels, several of these tags will appear in addition to the main hood label. They show the inspector exactly which panels were entered and on what date.

§ 12.6.14 The Two-Week Inspection Report

“After an inspection for grease buildup is complete, a written report shall be provided to the system owner or owner’s agent within 2 weeks.”

NFPA 96, 2024 Edition — Section 12.6.14

Section 12.6.14.1 lists six required items: (1) areas exceeding grease limits, (2) inaccessible areas not inspected, (3) accessible areas not inspected, (4) locations of duct access panels, (5) visible ductwork leakage, (6) leaking access panels. Items 2 and 3 are critical — they force disclosure of what wasn’t done. A report that omits them is incomplete on its face.

§ 12.6.15 The Two-Week Cleaning Report

“After cleaning is complete, a written report shall be provided to the system owner or owner’s agent within 2 weeks.”

NFPA 96, 2024 Edition — Section 12.6.15

Section 12.6.15.1 requires identification: date, technician name, provider details. Section 12.6.15.2 requires detail: inaccessible areas not cleaned, accessible areas not cleaned, access panel locations, ductwork leakage locations, and leaking access panels.

§ 12.6.16 Submission to the AHJ Where Required

“Where required, the reports required by 12.6.14 and 12.6.15 shall be submitted to the authority having jurisdiction.”

NFPA 96, 2024 Edition — Section 12.6.16

Some jurisdictions require the inspection and cleaning reports be submitted directly to the local fire marshal, not just kept on file. Whether this applies depends on your city. Where local rule requires it, Facilitec handles the submission.

For help with inspection preparation and service documentation, explore our NFPA compliance services.

FIELD NOTE
The single most useful item in the cleaning report — and the one most operators have never asked to see — is the inaccessible-areas list required by Section 12.6.15.2. A report that does not list inaccessible or skipped areas is usually a report that did not look very hard. The companion guide on what belongs in a real NFPA 96 cleaning report and what the service label should say walks through every required item by section.
Equipment Requirements

§ 6.1 Grease Removal Devices (Filters)

The filters inside the hood are formally called grease removal devices — the first line of defense between the cookline and the ductwork. NFPA 96 requires they be provided, listed (typically to UL 1046), and installed correctly so grease drains into the collection track. Damaged, missing, or non-listed filters are common citation triggers. Operating a filter-equipped exhaust system with filters removed also violates Section 12.1.2.

FIELD NOTE
The filter conversation is the operator-side conversation Section 6.1 does not have. Filter cleaning belongs to the kitchen staff on a daily or weekly cadence — not the professional service provider. Filters loaded with grease between professional visits stop catching grease, which sends raw grease into the ductwork and accelerates how quickly the next inspection finds threshold-crossing accumulation. The companion guide on commercial kitchen grease filters as a first line of defense covers the operator-side procedure.

§ 7.8.2.1 Rooftop Grease Containment

Section 7.8.2.1 lists nine requirements for rooftop terminations. Three drive most of the grease containment conversation:

• Subsection (4) — A noncombustible, closed, rainproof grease collection container.

• Subsection (5) — A grease collection device that doesn’t inhibit fan performance.

• Subsection (8) — A hinged upblast fan with flexible weatherproof electrical cable and a service hold-open retainer.

Grease that accumulates on the roof wasn’t contained. It damages roofing membranes, voids roof warranties, and creates fire fuel near the rooftop fan discharge.

FIELD NOTE
Rooftop grease pooling is one of the easiest deficiencies a fire marshal can verify — they walk to the roof, look at the area around the fan discharge, and document what they see. Buildings without containment hardware almost always have grease tracking down the parapet wall onto the roof membrane, which is both a fire risk under Section 7.8.2.1 and a roof-warranty issue separately. The Grease Containment service category covers the hardware side; the operator-side weekly check under Section 12.6.17 covers the maintenance side.

§ 8.1.6.3.1 • 8.1.6.3.2 Exhaust Fan Access for Cleaning

“Upblast fans shall be supplied with an access opening of a minimum 3 in. by 5 in. (76 mm by 127 mm) or a circular diameter of 4 in. (101 mm) on the curvature of the outer fan housing to allow for cleaning and inspection of the fan blades.”

NFPA 96, 2024 Edition — Section 8.1.6.3.1

“On existing upblast fans where sufficient access is not available to allow for the removal of grease contamination, an approved hinge mechanism or access panel shall be installed.”

NFPA 96, 2024 Edition — Section 8.1.6.3.2

If your rooftop fan can’t be safely lifted or accessed for inspection, that’s a citation waiting to happen — and a retrofit that must be completed before the next inspection can be considered complete.

Chapter 15 • Table 12.4 Solid Fuel Cooking Operations

Solid-fuel cooking — wood-fire pizza, BBQ smokehouses, charcoal grills, wood-pellet cookers — gets the tightest inspection cadence in NFPA 96 because solid fuel produces creosote and ash deposits in addition to grease. Table 12.4 sets inspection at monthly for any system serving a solid-fuel operation.

Chapter 15 adds equipment-side requirements around spark arrestors, separate ducting, and hood sizing. Spark arrestor filters must be cleaned at the same monthly cadence as the rest of the system.

FIELD NOTE
The reason solid-fuel cooking gets the tightest inspection cadence is that creosote and ash accumulate faster than ordinary grease, and the combustion temperatures inside the system run higher. A solid-fuel kitchen on a quarterly schedule is operating at four times the Table 12.4 cadence — and is the most common solid-fuel deficiency pattern fire marshals cite. Monthly inspection is the floor, not a recommendation.
Related Recurring Cycles

§ 12.2.1 • § 12.2.4 Fire Suppression System — Every Six Months

“Maintenance of the fire-extinguishing systems… shall be made by properly trained, qualified, and certified person(s) acceptable to the authority having jurisdiction at least every 6 months.”

NFPA 96, 2024 Edition — Section 12.2.1

Fusible links — the metal-alloy parts that trigger the system at a set temperature — must be replaced at least annually under Section 12.2.4. This work requires a licensed fire suppression contractor. A common compliance gap: hood cleaning current, suppression service overdue. The suppression service tag is one of the first things a fire marshal checks.

§ 12.1.4 Employee Fire-Safety Training

“Instructions shall be provided to new employees on hiring and to all employees annually on the use of portable fire extinguishers and the manual actuation of the fire-extinguishing system.”

NFPA 96, 2024 Edition — Section 12.1.4

Section 12.1.4.1 places responsibility on kitchen management. Section 12.1.4.2 requires records to be maintained and available to the AHJ. Section 12.1.4.3 requires instructions for manual system activation to be posted conspicuously in the kitchen. A kitchen with no training records on file is a citation waiting to happen — regardless of how clean the hood is.

§ 12.6.17 Grease Drip Containers — Inspected Weekly

“Metal containers used to collect grease drippings shall be inspected or emptied at least weekly.”

NFPA 96, 2024 Edition — Section 12.6.17

Usually a kitchen staff task rather than a contractor task — but a missed grease container is a frequent citation source.

§ 12.7.1 Cooking Equipment Annual Service

“Inspection and servicing of the cooking equipment shall be made at least annually by properly trained and qualified persons.”

NFPA 96, 2024 Edition — Section 12.7.1

This comes from the equipment vendor or a kitchen equipment service provider — separate from the hood cleaning cycle. The hood cleaning crew may flag obvious equipment issues during their visit, but full equipment service is its own recurring obligation.

ENFORCEMENT & CONSEQUENCES

ENFORCEMENT Penalties, Fines, and Consequences of Non-Compliance

NFPA 96 is not a self-enforcing document. The penalties for falling out of compliance come from the local fire code that adopts NFPA 96, from the insurance policy that references it, and from the operational consequences of a grease fire when one happens. Operators searching for “what happens if I fail” deserve a direct answer — so this section pulls together the enforcement reality from across the Southwest.

Grease fires destroy buildings. They end businesses. They put lives at risk. The enforcement framework exists because those outcomes are real — and the cost of a clean compliance file is a small fraction of the cost of a single grease fire claim.

Reinspection Fees from the Fire Marshal

When the fire marshal cites a deficiency, the kitchen has a deadline to correct it, and the marshal returns for a reinspection. Each city sets its own reinspection fee schedule. The Dallas Fire-Rescue schedule is representative of major Texas metros:

REINSPECTIONFEE
First reinspection$171
Second reinspection$200
Third reinspection (and beyond)$255
Penalties upon convictionUp to $2,000

The fees compound. A kitchen that fails the first reinspection because the corrective work was incomplete pays the second-visit fee on top of the first. A repeat at the third visit risks the conviction penalty. Houston, Austin, San Antonio, and the other major metros each set their own schedules through their city fire department’s fire marshal’s office — the rates vary but the structure is consistent. The companion guide on what happens after a failed fire marshal inspection walks through the deficiency-response process in detail.

Forced-Closure Scenarios

A deficiency notice does not automatically close the kitchen. Most citations allow continued operation while corrections are made. A handful do not:

  • Non-functioning fire suppression system on an active cooking appliance. The marshal can issue an order to stop using that appliance until the system is restored under Section 12.2.1.
  • Severe grease accumulation in the ductwork. When the inspection finds grease loaded heavily enough to constitute an active fire hazard, the marshal can require cleaning before further cooking on the affected hood.
  • Repeated failure to maintain compliance. When a kitchen has failed multiple reinspections on the same citation, the marshal can escalate to municipal code-enforcement action, which can include operating-permit suspension.

The deficiency notice itself specifies the conditions. The marshal’s office will clarify the timeline when called.

Insurance Claim Consequences

An overdue inspection or a missing report does not automatically void coverage. It changes how a claim is handled. After a commercial kitchen fire, the carrier’s investigator typically pulls the most recent inspection report, the most recent cleaning report, and the service label on the hood — then evaluates whether the recurring schedule matched the kitchen’s cooking volume against the inspection schedule in Table 12.4. A complete file moves the investigation quickly. A file with gaps extends the investigation and can affect the coverage outcome. Coverage decisions are always governed by the specific policy language. The companion guide on what an insurance carrier wants to see in a hood cleaning file covers the documentation set carriers actually request.

General Fine Ranges Across Jurisdictions

Most municipal fire code violations carry civil penalty ranges from a few hundred dollars per occurrence at the entry level up to ten thousand dollars or more for serious or repeated violations. Specific amounts vary by city and by the type of citation. Dallas, Houston, Austin, San Antonio, Oklahoma City, Tulsa, New Orleans, Shreveport, Albuquerque, and the smaller metros across the Southwest each set their own schedules. Most kitchens never approach the upper end because the deficiency-correction cycle resolves the issue long before it escalates. The risk profile changes when a kitchen consistently fails reinspections or when a fire occurs while a kitchen is out of compliance.

The Operational Cost of a Grease Fire

None of the fee or penalty numbers above approach the cost of a single commercial kitchen fire when one occurs. Property damage alone can run into seven figures for a structural fire that involves the building’s ventilation and roof systems. Business interruption — the lost revenue while the kitchen rebuilds — typically extends six to twelve months for a full restoration. Replacement of cooking equipment, hood, ductwork, and rooftop fan can take longer when supply chains are tight. Insurance covers most of it for a kitchen with a clean compliance file; a kitchen with documentation gaps faces extended claims handling at exactly the moment cash flow has stopped.

FIELD NOTE
The kitchens that consistently pass inspections without scrambling are the kitchens whose documentation file is built at the service visit, not the day before the marshal arrives. The five-citation patterns Facilitec Southwest sees most often across the Southwest — grease past the depth limits, missing or expired service label, no written report inside the two-week window, blocked or untagged access panels, and overdue fire suppression service — all close at the cadence level, not the deficiency-response level. The companion guides on the pre-inspection checklist and how often a commercial kitchen exhaust system should be cleaned walk through the prevention side in detail.
Enforcement references: Dallas Fire-Rescue, Prevention and Investigation Bureau (current reinspection fee schedule); 2021 International Fire Code with Dallas amendments effective February 10, 2023; 2021 International Mechanical Code with Dallas amendments effective May 12, 2023. Fee schedules reflect publicly available rates at the time of writing; verify with the AHJ at the time of reinspection. Insurance practice descriptions reflect typical commercial restaurant program underwriting; specific carrier and policy requirements vary. Facilitec Southwest is not an insurance advisor; coverage outcomes are governed by the specific policy.

Common Questions About NFPA 96

What is NFPA 96?

NFPA 96 is the National Fire Protection Association’s Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations — the national rulebook for commercial cooking hoods, ducts, exhaust fans, and fire-suppression systems. Fire marshals enforce it; insurance carriers reference it. The current edition in 2026 is the 2024 edition.

Section 4.1.5.1 names the equipment owner as responsible by default. Section 4.1.5.2 allows delegation in writing through the lease or a management contract. The lease language determines who holds the obligation.

NFPA 96 sets an inspection schedule (Table 12.4) and a cleaning trigger (Section 12.6.1.1 grease-depth thresholds), not a fixed cleaning schedule. Inspection is monthly for solid fuel, quarterly for high-volume, semiannually for moderate-volume, annually for low-volume. Cleaning is required when grease exceeds the applicable threshold.

Section 12.6.1 requires a “properly trained, qualified, and certified person(s) acceptable to the authority having jurisdiction.” The two most recognized credentials across the US are IKECA’s CECS and Phil Ackland Training. Facilitec Southwest is Phil Ackland Certified.

Three pieces: a service label on the hood (Section 12.6.13), a service tag near each opened access panel (Section 12.6.10), and a written report to the kitchen owner within two weeks (Section 12.6.15 for cleaning, Section 12.6.14 for the inspection).

At least every six months by a certified person (Section 12.2.1). Fusible links must be replaced at least annually (Section 12.2.4).

Yes. Section 12.1.4 requires new employees be trained on hire, and all employees trained annually, on portable fire extinguishers and manual activation of the fire suppression system. Records must be maintained and available to the AHJ.

At least weekly. Section 12.6.17 requires metal containers used to collect grease drippings to be inspected or emptied at minimum once per week.

Penalties come from the local fire code that adopts NFPA 96, not from the standard itself. Most major Texas metros operate on a tiered reinspection fee schedule plus potential civil penalties for unresolved violations. Dallas Fire-Rescue currently charges $171 for the first reinspection, $200 for the second, and $255 for the third and beyond, with penalties upon conviction up to $2,000. Houston, Austin, San Antonio, and the other Southwest metros set their own rates. Severe deficiencies — a non-functioning fire suppression system on an active appliance, for example — can also result in an order to stop using the affected appliance until corrections are made.

A typical deficiency notice does not close the kitchen — corrections are made while the kitchen stays open, and reinspection follows. A non-functioning fire suppression system on an active cooking appliance can result in an order to stop using that appliance until the system is restored. Repeated reinspection failures on the same citation can escalate to municipal code-enforcement action, which can include operating-permit suspension. The deficiency notice itself specifies the timeline and conditions.

No. NFPA 96 is a standard, not a statute. It does not impose fines or penalties on its own. Penalties come from the local fire code that adopts NFPA 96 — typically the International Fire Code or the International Mechanical Code as adopted by the city or county — and from insurance policy provisions that reference the standard. The AHJ is the local fire marshal or fire-code office with enforcement authority.

Related Reading

Companion Guides

Sources and notes: NFPA 96, 2024 Edition. Sections cited: 4.1.5.1–4.1.5.2; 6.1; 7.8.2.1; 8.1.6.3.1–8.1.6.3.2; 12.1.2; 12.1.4.1–12.1.4.3; 12.2.1; 12.2.4; 12.4 and Table 12.4; 12.6.1; 12.6.1.1.1–12.6.1.1.4; 12.6.2; 12.6.3; 12.6.6–12.6.9; 12.6.10; 12.6.11–12.6.12; 12.6.13.1–12.6.13.2; 12.6.14.1; 12.6.15.1–12.6.15.2; 12.6.16; 12.6.17; 12.7.1; Chapter 15. Enforcement references: Dallas Fire-Rescue Prevention and Investigation Bureau (current reinspection fee schedule); 2021 International Fire Code with Dallas amendments effective February 10, 2023; 2021 International Mechanical Code with Dallas amendments effective May 12, 2023. Verbatim section text is quoted; supporting explanation reflects Facilitec Southwest field experience with commercial cooking establishments across the Southwest since 1986. Facilitec Southwest is not an insurance advisor; coverage outcomes are governed by the specific policy. This page is a reference, not legal or AHJ-specific advice; verify local requirements with the local fire marshal. Facilitec Southwest follows NFPA 96 guidelines for cleaning and inspection of grease buildup.

Every NFPA 96 Section. Handled at Every Visit.

Schedule NFPA 96-compliant* hood cleaning with Phil Ackland Certified Technicians. From Cooktop to Rooftop, since 1986.

Request A Quote

By providing your phone number, you consent to receive SMS messages from Facilitec Southwest. Message frequency varies. Message & data rates may apply. Text HELP to1 817-785-9128 for assistance. Reply STOP to unsubscribe.