8 Questions Every Kitchen Should Be Able to Answer Before December: The Kitchen Exhaust Checklist

Restaurant staff member decorating a dining area with Christmas garlands and ornaments, preparing a welcoming atmosphere for holiday dining
Eight questions about your kitchen exhaust system — hood, duct, fan, roof, paperwork, and filters — to answer before December, with the NFPA 96 section behind each one.

OPERATIONS & EQUIPMENT · OPERATOR CHECKLIST

Two weeks from now your kitchen will be running harder than at any other point in the year. The question isn’t whether the exhaust system can handle it — it’s whether you know, today, what condition it’s in. Most operators can answer two or three of the eight questions below from memory. The ones they can’t answer are usually the ones the fire marshal asks first.

November 17, 2026 · By Facilitec Southwest

QUICK ANSWER

Before the holiday surge, every commercial kitchen should be able to answer eight questions about its exhaust system: (1) the date of the last professional cleaning, (2) whether the cleaning frequency matches the cooking volume under NFPA 96 Table 12.4, (3) whether a current service label is on the hood per Section 12.6.13, (4) whether every access panel is tagged per Section 12.6.10 and reachable per Section 12.6.4, (5) whether the rooftop fan is running normally with its hinge kit intact per Section 8.1.1.1, (6) whether rooftop grease is contained per Section 7.8.2.1, (7) whether the written report from the last service per Section 12.6.15 is on file and findable, and (8) whether the crew’s daily filter routine is actually happening. Seven of the eight are about the system and its paperwork; the eighth is about the people. An operator who can answer all eight with a date, a document, or a name is ready for December. An operator who can’t has two weeks to get the answers — and November is the month to book the service that produces them.

A SECOND SET OF EYES

Can’t answer all eight? Facilitec Southwest will walk your exhaust system — hood, duct, fan, roof, and file — and tell you exactly where you stand before December, across TX, OK, LA, NM, and AR.

Request a System Walk-Through →

The Checklist

Print this section, take it into the kitchen and up to the roof, and check off what you can answer with a date, a document, or a name. Anything you can’t check is the to-do list for the next two weeks. The sections that follow explain each question — what it’s asking, where it comes from in NFPA 96, and what a good answer looks like.

8 QUESTIONS BEFORE DECEMBER — KITCHEN EXHAUST SYSTEM
  • 1. When was the last professional cleaning?
    Exact date. From the service label or the written report, not from memory.
  • 2. Is the cleaning frequency right for your cooking volume?
    Table 12.4: monthly (solid fuel), quarterly (high volume: charbroil, wok, 24-hr), semiannual (moderate), annual (low). Holiday volume moves you up a category.
  • 3. Is there a current service label on the hood?
    Section 12.6.13. Company, technician, date. Legible. Within your cadence.
  • 4. Are the access panels tagged and reachable?
    Sections 12.6.4 and 12.6.10. Every panel, not just the ones you can see from the kitchen. Nothing stored in front of them.
  • 5. Is the fan running normally?
    No vibration, no new noise, smoke clears the kitchen as it used to. Hinge kit present per Section 8.1.1.1.
  • 6. Is rooftop grease contained?
    Section 7.8.2.1. Containment system at the fan, serviced at the last cleaning. No grease on the roof surface or at the roof drain.
  • 7. Is the written report on file?
    Section 12.6.15. The report from the last service, where you can find it in under two minutes.
  • 8. Is the filter routine happening?
    Your crew’s job, not the vendor’s. Named person per shift, on the closing checklist, spare set on hand.

This checklist is an operational self-assessment tool, not an NFPA 96 inspection. Inspection for grease buildup under Section 12.6.1.1 must be performed by a properly trained, qualified, and certified person. Phil Ackland Certified Technicians follow NFPA 96, 2024 Edition guidelines for cleaning and inspection of grease buildup. Filter cleaning is the operator’s responsibility; available as an optional add-on. Facilitec Southwest · 2300 Cold Springs Rd, Fort Worth, TX 76106 · (866) 466-3339

1. When Was the Last Professional Cleaning?

Not “sometime this summer.” The date. It’s on the service label on the hood and on the written report, and if you have to look it up, that’s fine — the point is that it can be looked up.

This question matters more in November than at any other time because of what happens next. Our post on holiday season hood cleaning walks through why the eight weeks from Thanksgiving to New Year’s load an exhaust system faster than the rest of the year: volume doubles, menus shift toward roasting and frying, staff are stretched. A kitchen last cleaned in late summer will absorb all of that on top of three months of normal deposits before a January inspection catches it.

LAST CLEANING DATEWHERE YOU STANDWHAT TO DO
Within the last 30 daysGood — the system starts the season near baselineSchedule a post-Thanksgiving inspection; book January now
31–90 days agoWithin a quarterly cadence, but December’s volume will push the system past threshold before the next scheduled inspectionBook a November baseline cleaning this week; vendor calendars fill from mid-month
More than 90 days agoOutside a quarterly cadence already; the holidays will compound itBook the earliest available cleaning; treat it as urgent
Don’t knowNo label, no report, or neither findableThat’s questions 3 and 7 — and it means booking a cleaning and starting the file over

2. Is the Cleaning Frequency Right for Your Cooking Volume?

NFPA 96 doesn’t say “clean quarterly.” It says inspect on a schedule set by Table 12.4 — by what and how much you cook — and clean when the inspection finds grease at the threshold in Section 12.6.1.1. Our posts on how often to clean a commercial kitchen exhaust system and inspection vs. cleaning cover the distinction in full. For the checklist, the question is simpler: does the cadence on your contract match the category your kitchen is actually in?

TABLE 12.4 CATEGORYINSPECTION FREQUENCYTYPICAL KITCHENS
Solid-fuel cookingMonthlyWood-fired, charcoal, smokers — see Chapter 14
High-volume cookingQuarterly (monthly is common for charbroiling and wok)24-hour operations, charbroiling, wok cooking, hospitals, high-volume restaurants
Moderate-volume cookingSemiannually (quarterly is the common contract floor)Most full-service restaurants, hotel restaurants, cafeterias
Low-volume cookingAnnuallyChurches, day camps, seasonal businesses, senior centers with light cooking

Two things change the answer. First, a menu change: adding a charbroiler, a fryer program, or a smoker for the holidays moves the category and nobody tells the vendor. Second, the holidays themselves: a moderate-volume kitchen operates at high-volume rates for eight weeks. If your contract cadence was set when the kitchen opened and the menu has changed since, the answer to question 2 is “no” even if the vendor shows up on schedule.

3. Is There a Current Service Label on the Hood?

Section 12.6.13 requires that after each inspection or cleaning, a label be applied to the hood showing the name of the servicing company, the name of the person who did the work, and the date. It’s the first thing a fire marshal looks at — before the duct, before the filters, before anything. A current label within your cadence ends the conversation; a missing or expired label starts a longer one.

  • Present. On the hood, in a visible location, not peeled off during a deep clean of the exterior.
  • Legible. Labels fade under heat and grease. If the date can’t be read, it doesn’t count.
  • Complete. Company, technician, date. A label with just a company logo and a date is missing the qualified-person element of Section 12.6.1.
  • Within cadence. A label dated outside your Table 12.4 frequency is evidence of non-compliance, not evidence of compliance.

Our post on what’s in a real NFPA 96 cleaning report and what the service label should say covers the label and the report together.

FIELD NOTE — THE LABEL ON THE WRONG HOOD

A restaurant with three hoods had one service label — on the hood closest to the kitchen door. The fire marshal asked about the other two. The operator said the vendor cleaned all three. The vendor’s report confirmed it. But Section 12.6.13 is per hood, and two hoods with no label looked, to the inspector, like two hoods that had never been serviced. The correction was a phone call and two labels. The inspection took forty minutes longer than it needed to.

4. Are the Access Panels Tagged and Reachable?

Section 12.6.4 requires that the entire exhaust system be accessible for inspection and cleaning. Section 12.6.10 requires that access panels be marked so inspectors can find them. Together they’re the most-cited deficiency in the standard, and the one most operators have never thought about — because the panels are above the ceiling, on the roof, or behind a wall. Our post on the access panel rule explains why “we cleaned everything accessible” isn’t a compliant answer.

For the checklist, the question has three parts:

  1. Do you know where every panel is? The hood survey from your vendor should show the duct route and every access point. If you don’t have a survey, you don’t know whether the duct has panels at all.
  2. Is every panel tagged? A label on each panel identifying it as a kitchen exhaust access point, so an inspector in the ceiling plenum or on the roof can find it.
  3. Is every panel reachable? Nothing stored in front of it, nothing built over it since the last service, ceiling tile removable, roof hatch unlocked. A tagged panel behind a stack of chairs is not accessible.

5. Is the Fan Running Normally?

The rooftop exhaust fan is the part of the system operators see least and depend on most. When it slows, grease stops leaving the duct. When it stops, the kitchen fills with smoke and the suppression system becomes the only thing between a flare-up and a fire. Three things to check from the kitchen, one from the roof:

  • Does smoke clear the way it used to? A kitchen that’s hazier than it was in the summer has a fan problem, a filter problem, or a duct-loading problem — and all three get worse in December.
  • Any new noise or vibration? A belt slipping, a bearing going, a blade unbalanced by grease buildup. The sound usually changes before the fan fails.
  • Is the hood capturing at the edges? Grease-laden vapor rolling out from under the hood canopy means the fan isn’t pulling enough air.
  • On the roof: is the hinge kit in place? Section 8.1.1.1 requires upblast fans to be hinged so they can be tilted for cleaning without disconnecting the ductwork. A fan without a hinge kit can’t be fully cleaned, and fire marshals cite it. See the hinge kit post.

A fan that’s failing in November will fail in December. Our post on exhaust fan repair vs. replace covers the decision; the checklist question is just whether anything has changed.

6. Is Rooftop Grease Contained?

Every exhaust fan throws grease. Section 7.8.2.1 requires that grease draining from the fan be collected in a closed, noncombustible container rather than discharged onto the roof — which is what rooftop grease containment systems exist to do. Uncontained grease on a roof is a fire hazard (fuel at the point a duct fire exits the building), a roof-membrane problem (grease degrades EPDM, TPO, and modified bitumen and voids roofing warranties), and a stormwater violation (rain carries it to the roof drain and into the storm sewer).

WHAT YOU SEE ON THE ROOFWHAT IT MEANSWHAT TO DO
Containment system at the fan, pads or box cleanContained and recently servicedConfirm it’s on the vendor’s service scope for the next cleaning
Containment system present, pads saturated or box overflowingContained but overdue for serviceService before December — a saturated pad is no longer containing anything
No containment, grease film on the roof around the fanUncontained; roof damage and stormwater exposure accumulatingInstall containment; clean the roof surface with capture; document the condition for the landlord
Grease trail from the fan toward a roof drainActive discharge to the storm sewer every time it rainsUrgent — containment, roof cleaning, and a conversation with whoever manages the building

Our posts on rooftop grease containment and where the grease goes cover the systems and the environmental rules. If you lease, our landlord-or-tenant post covers who’s responsible for the roof.

7. Is the Written Report on File?

Section 12.6.15 requires that after cleaning, the servicing company provide a written report to the owner or operator identifying what was cleaned, what wasn’t and why, and any deficiencies found. The label on the hood says a service happened. The report says what the service was. Fire marshals ask for it at inspection; insurance carriers ask for it at renewal; landlords ask for it under the lease; and after a fire, the adjuster asks for it first.

The checklist question has a time limit built in: can you find it in under two minutes? A report in a binder in the office, in the compliance software, or in an email folder you can search counts. A report “the vendor has” or “somewhere in the manager’s desk” doesn’t.

  • Most recent report — dated, matching the service label
  • Areas cleaned and areas not cleaned — if the report says “duct cleaned where accessible,” question 4 is also a “no”
  • Deficiencies noted — missing panels, hinge kit, containment, fan condition — and whether they’ve been corrected
  • Prior reports — three years is the common retention expectation; insurance carriers often want to see the pattern, not one date

Our post on what your insurance carrier wants to see in your hood cleaning file covers the file from the underwriter’s side — and renewal questionnaires for January 1 policies go out this month.

THE TWO-MINUTE RULE

If the fire marshal, the insurance adjuster, or the landlord asked for your last exhaust cleaning report right now, could you hand it to them in two minutes? If yes, question 7 is answered. If no, the answer is “no” regardless of whether the report exists.

8. Is the Filter Routine Happening?

Seven of these questions are about the system and its paperwork. This one is about your crew. NFPA 96 puts inspection and cleaning of the exhaust system on a certified contractor — and leaves the grease filters to the operator. Baffle filters are the first line of defense: they catch grease before it enters the duct, and when they’re loaded they stop catching it and start passing it. Everything that passes goes into the duct and stays there until the next professional cleaning.

The holidays are when the filter routine breaks. New seasonal staff don’t know the filters come out. Closing crews are exhausted. The hood gets wiped on the outside and nobody pulls a baffle for three weeks. Our post on commercial kitchen grease filters covers the daily routine. For the checklist, the question is whether the routine survives December:

  1. Is filter cleaning assigned to a named person per shift? Not “closing crew.” A name on the closing checklist with a sign-off.
  2. Is there a spare set of filters? So a loaded set is swapped and soaked rather than skipped because there’s no time at 1 am.
  3. Have seasonal hires been shown the hood? Where the filters are, how they come out, what the grease cup is, who to tell if the hood is dripping.
  4. Does someone look up? Grease dripping from the hood edge or filter track, smoke lingering that used to clear, a film on the roof around the fan — the three signs the duct is loading faster than the cadence assumes.

If the kitchen can’t sustain daily filter cleaning through December, a filter exchange service for the season is a reasonable option. Our post on hood cleaning vs. filter exchange explains what that service covers and what it doesn’t.

FIELD NOTE — THE CHECKLIST NOBODY SIGNED

A restaurant we service had a laminated closing checklist on the wall by the dish pit with “clean hood filters” as item nine of twelve. It had a column for initials. The column was empty for six weeks — from the first week of November through mid-December. Nobody had stopped cleaning the filters on purpose; three new closers had started in that window, none had been told that item nine meant pulling the baffles, and the manager who used to check the sheet was working doubles. We found out because the duct above that hood was at threshold five weeks after a bare-metal cleaning. The fix was a name instead of a job title on the checklist and a two-minute demonstration for every new hire. The duct made it to January the following year.

Scoring the Checklist

Eight questions, each answered with a date, a document, a name, or a “no.” What the score means:

SCOREWHERE YOU STANDBEFORE DECEMBER
8 of 8The system is documented, maintained, and staffed. The fire marshal’s holiday walk-through is a formality.Book the post-Thanksgiving inspection and the January reset if they aren’t already on the calendar
6–7 of 8Typical for a well-run kitchen; the gaps are usually question 4 (panels) or question 6 (roof) — the parts of the system nobody seesClose the gaps in the next two weeks; most are a vendor visit or a phone call
4–5 of 8The system may be compliant but you can’t prove it, and the holidays will widen every gapBook a November cleaning with a full survey; start the file over from that report
3 or fewerYou don’t know the condition of the exhaust system going into the highest-volume weeks of the yearTreat it as urgent. Cleaning, survey, containment, label, report — this month

Most operators land at six or seven. The two questions that trip up well-run kitchens are the panels and the roof, because they’re the parts of the system that live outside the kitchen and outside the operator’s daily line of sight. That’s what a second set of eyes is for.

SIGNATURE APPROACH

From Cooktop to Rooftop, our Phil Ackland Certified Technicians answer all eight questions on one visit — the cleaning date, the Table 12.4 cadence for your actual menu, the label on every hood, every access panel tagged and opened, the fan tilted on its hinge kit, containment serviced, the written report in your hand before we leave, and a walk-through of the filter routine with whoever closes. The outcome is a Grease-Free and Fire-Safe kitchen through the busiest weeks of the year, and the peace of mind that comes with it.

Frequently Asked Questions

What should I check on my kitchen exhaust system before the holidays?

Eight things: the date of the last professional cleaning; whether the cleaning frequency matches your cooking volume under NFPA 96 Table 12.4; whether a current service label is on every hood; whether every access panel is tagged and reachable; whether the fan is running normally with its hinge kit in place; whether rooftop grease is contained; whether the written report from the last service is on file and findable; and whether your crew’s daily filter routine is actually happening.

Is this checklist the same as an NFPA 96 inspection?

No. This is an operator self-assessment — a way to find out what you know and don’t know about your system before December. Inspection for grease buildup under NFPA 96 Section 12.6.1.1 must be performed by a properly trained, qualified, and certified person, and cleaning to bare metal under Section 12.6.5 is contractor work. The checklist tells you whether to book that work; it doesn’t replace it.

Where do I find the date of my last hood cleaning?

On the service label on the hood, required by NFPA 96 Section 12.6.13, and on the written report required by Section 12.6.15. If neither exists or neither can be found, you don’t have a documented date — and the practical answer is to book a cleaning and start the file from that report.

How do I know if my cleaning frequency matches my cooking volume?

Compare your contract cadence to NFPA 96 Table 12.4: monthly for solid-fuel cooking and typically for charbroiling, wok, and 24-hour operations; quarterly for high-volume; semiannual for moderate; annual for low. Then ask whether the menu has changed since the cadence was set — a charbroiler, fryer program, or smoker added for the holidays moves the category — and whether holiday volume pushes a moderate kitchen into high-volume territory for the season.

What does the service label on the hood have to show?

Per NFPA 96 Section 12.6.13: the name of the servicing company, the name of the person who performed the work, and the date of the inspection or cleaning. One label per hood, legible, within your cadence. A label that’s missing, faded, incomplete, or dated outside the cadence doesn’t satisfy the section.

Why are access panels on the checklist if I can’t see them?

Because the fire marshal will look for them, and because a duct that can’t be opened can’t be cleaned. NFPA 96 Section 12.6.4 requires the entire system to be accessible, and Section 12.6.10 requires panels to be marked. The hood survey from your vendor shows where every panel is; the checklist asks whether each one is tagged and whether anything has been stored or built in front of it since the last service.

How do I know if the exhaust fan is running normally?

From the kitchen: smoke clears the way it used to, no new noise or vibration, no grease-laden vapor rolling out from under the hood edge. From the roof: the fan is level, the hinge kit required by Section 8.1.1.1 is in place, and there’s no grease pooling in the housing. A fan that’s changed since summer is a fan to have looked at before December.

What is rooftop grease containment and do I need it?

A system at the fan — collection box, absorbent pads, or perimeter berm — that catches grease the fan discharges so it doesn’t reach the roof surface or the roof drain. NFPA 96 Section 7.8.2.1 requires grease draining from the fan to be collected in a closed, noncombustible container. Most Southwest fire marshals, landlords, and insurers expect containment on any commercial kitchen fan; grease on the roof is a fire hazard, a roof-warranty problem, and a stormwater violation.

What goes in the written report, and how long do I keep it?

Per NFPA 96 Section 12.6.15: what was cleaned, what wasn’t and why, and any deficiencies found. Keep every report; three years is the common retention expectation from insurance carriers and landlords, and after a fire the adjuster will want the whole history. The checklist test is whether you can hand over the most recent one in under two minutes.

Is filter cleaning the vendor’s job or mine?

Yours. NFPA 96 puts exhaust system inspection and cleaning on a certified contractor and leaves grease filter maintenance to the operator. Daily or per-shift filter cleaning is what keeps grease out of the duct between professional services. If the kitchen can’t sustain it through December, a filter exchange service is a reasonable seasonal option — but it’s a separate service from hood cleaning.

I can only answer four of the eight. What should I do first?

Book a cleaning with a full hood survey this month. One visit answers questions 1, 3, 4, 5, 6, and 7 — the technician dates and labels every hood, opens and tags every panel, tilts the fan, services containment, and hands you the written report. Then set the cadence for your actual menu (question 2) and put a name on the filter routine (question 8). Four answers becomes eight in one service.

Would Facilitec Southwest walk my system and tell me where I stand?

Yes. We’ll walk the hood, duct, fan, roof, and file and give you a straight answer on all eight questions — what’s in order, what isn’t, and what to do before December. Service across TX, OK, LA, NM, and AR. Request a walk-through or see our NFPA compliance services.


NFPA 96, 2024 Edition — Table 12.4 (inspection frequency by cooking volume and type); Section 12.6.1 (properly trained, qualified, and certified person); Section 12.6.1.1 (inspection for grease buildup and cleaning trigger); Section 12.6.4 (accessibility of the entire exhaust system); Section 12.6.5 (cleaning to bare metal); Section 12.6.10 (access panel marking); Section 12.6.13 (service label contents); Section 12.6.15 (written report); Section 8.1.1.1 (hinged upblast fans); Section 7.8.2.1 (rooftop terminations and grease collection); Chapter 6 (grease removal devices) and operator responsibility for filter maintenance. This checklist is an operational self-assessment tool for owners and operators; it is not an NFPA 96 inspection and does not satisfy the inspection requirement of Section 12.6.1.1, which must be performed by a qualified person. Table 12.4 category descriptions are summarized; the standard’s exact wording and the AHJ’s interpretation govern. Report retention periods reflect common insurance carrier and landlord expectations rather than a requirement of NFPA 96. Field Notes describe composite service situations with identifying details changed. Phil Ackland Certified Technicians follow NFPA 96, 2024 Edition guidelines for cleaning and inspection of grease buildup. Filter cleaning is the operator’s responsibility; available as an optional add-on. This article is a compliance and operational reference, not legal, insurance, or AHJ-specific advice.